First do Hard Reset on the System.

If the Station is acting as it is trying to dim the lights then check for a possible dimmer issue.

First remove Pig Tail from Module that has the circuit that is not working.

Using a True RMS Meter Set on DC measure the following With Station at full on

Black Wire to Yellow Wire Should Be 12 VOLTS DC.

Blue Wire to Black Wire should be 5VDC

Red Wire to Black Wire Should be 5VDC

If none of these are present Replace Dimmer Service Card

Now set the station at half way.

Make the same measurments again

You should still have 12 Volts on the Black and yellow wires.

Red to Black should now be 2.5VDC

Blue to Black should now be 2.5VDC

If these voltages are correct and lights are still not dimming Plug Pigtail back in. Now there are LED”S on the driver board the red LED’s are for the Relays are they on if not then Driver board is bad. If they are the relay could be bad chec to see if relay is pulling in. If it is then Replace Duel SCR in Module. They can buy this at an Electronics parts house. Lead time is way to long.