Follow

All Panels - Available Current Draw from LC&D Devices

The current that is available to power occ-sensors is:

DigiLink                                  750 ma 12/24v

Blue Box DI                            200 ma 12/24v

iDH / iDIM                               500 ma 12/24v

Bus Booster                          800 ma 12v

The current that is available to drive 0-10 dimming

Per channel                           15 ma

Dimmer Distribution Card       250 ma per channel, channel can be ran together to a maximum of 1 Amp per card.