nLight Wiring with Integral Drivers

Fixtures that are nLight enabled are connected with normal power feed to an integral driver at the J-box at the beginning of the fixture run. CAT-5e cables that control (dim) the circuit connect to the RJ-45 connector on the fixture, typically at the other end of the fixture section from the power feed. It requires an embedded nLight controller (provided) for that fixture or set of fixtures.

 

Both line voltage and signal wires connect with plug-in connectors (provided) at fixture joints along the run.

 