Follow

Fresco - Using Multiple Fresco Panels in Auditoriums, Ball Room or similar application

Using Multiple Fresco Panels in Auditoriums or Ball Room type application.

 

To have more than 1 Fresco panel communicate across FCN network, ensure that the FCN connectors are daisy chained for each panel.

Once FCN communication is established via FCN Network connectivity

Go to SETUP --> CONTROLLER --> NETWORK ID (No change) --> CONTROLLER ID should be changed in increasing order.  The first Fresco panel will have controller ID 1, second Fresco panel will have controller ID 2 etc.

If controller IDs are not set correctly, the panels will not communicate across the FCN network.  Hence, it is important to change this prior to setting up Fresco Programming.

It is also important to turn termination ON on the first and last Fresco Panel.

 

Was this article helpful?
0 out of 0 found this helpful
Have more questions? Submit a request